|
Anovel
Single-phase electronic starter circuit meant for 0.5
HP and 1 HP motors, is presented. It incorporates both
over-load and short-circuit protections. A specially
made current sensing device has been added in this starter
to sense the current being drawn by the motor.
If the motor jams due to bearing failure or defect in
the pump or any other reason, then it would draw much
higher current than its normal rated current. This will
be sensed by the current sensing device, which will
trip the circuit and protect the motor. The other reasons
resulting in motor drawing higher current include:
(a) Windings damaged or short-circuit existing between
windings.
(b) Shorting of motor terminals by mistake.
(c) If under voltage or single phasing occurs in the
mains supply source (normally a 440V AC, 3 phase with
neutral - four wire system).
The main components used in the circuit comprise a specially
wound sensing transformer X1, another locally available
step-down transformer X2, one single change-over relay
RL1, two 2-change-over relays (RL2 and RL3) and other
discrete components as shown in the figure. The mains
supply to the motor is routed in series with primary
of transformer T1 via normally open contacts of relay
RL3. The primary of transformer X1 is connected in the
neutral line. To switch on the supply to the motor,
momentarily switch S1 is to be pressed, which causes
the supply path to transformer X2 primary to be completed
via N/C contacts of relay RL1. The relay RL2 gets energised
due to the DC voltage developed across capacitor C2
via the bridge rectifier. Once relay RL2 energises,
the N/O contacts RL2(a) provide a short across switch
S1 and hence supply to the primary of transformer X2
becomes continuous and hence relay RL2 latches even
if switchS1 is subsequently open. The other N/O contacts
RL2(b) of relay RL2, on energisation, connects the voltage
developed across capacitor C2, to relay RL3, which thus
energises and completes the supply to the motor as long
as current passing through primary of transformer X1
is within limits (for a 1-hp motor). When the current
drawn by motor exceeds the limit, the voltage developed
across secondary of transformer T2 is sufficient to
energise relay RL1 and trip the supply to relays RL2
and RL3 which was passing via the N/C contact of relay
RL1. As a result the supply to the motor also trips
The
contact rating for relays RL1 and RL2 should be 5 amperes,
while contact ratings of relay RL3 should be 10 to 15
amperes. The transformer X1 can be wound using any suitable
size CRGO core. (One can use a burnt out transformer
core as well). The primary comprises of 30 to 31 turns
for use with 1-HP motor and additional 8turns, if you
are using a 0.5 HP motor. The fuses F1 and F2 are kit-Kat
type. The ON push button is normally ‘off’ type, while
off push button S2 is of normally ‘on’ type. Capacitors
C1 and C2, apart from smoothing the rectified output,
provide necessary delay during energisation and de-energisation
of relays. Diodes across relays are used for protection
as free wheeling diodes.
Starters
for 0.5 HP and 1 HP motors are not easily available
in the market. Users are therefore compelled to use
10 Amp rated circuit breaker for such motors. A mechanical
starter or auto starter would turn out to be costlier
than the circuit given here, which works very reliably.
The author has been using such an electronic starter
with 1 HP pump set for nearly a year without any problem.
Parts used in this circuit are easily available in most
of the local markets.
|